Skip to Main Content
Search distributed energy resources in New York

Remeeder House - Sheffield

Overview Remeeder House - Sheffield

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Jun 2017 to Apr 2022
700
MWh
electricity generated
Capacity
Factor
8,977
Mcf
generator fuel consumed
Electric
Efficiency
4,284
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Jun 2017 to Apr 2022
Electricity Generated (kWh) Total Fuel Consumed (cf) Total Heat Used (MBtu) Heat Rejected (MBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 699,654 8,976,603 4,283,658 0 46.8 25.8 46.2 72.0
Jun 2017
14,960 185,501 0 0 59.4 26.7 0.0 26.7
Jul 2017
17,730 220,190 0 0 68.1 26.6 0.0 26.6
Aug 2017
16,945 212,815 0 0 65.1 26.3 0.0 26.3
Sep 2017
19,953 243,634 40,091 0 79.2 27.1 15.9 43.0
Oct 2017
16,551 212,571 113,138 0 63.6 25.8 51.6 77.3
Nov 2017
19,401 238,778 130,273 0 77.0 26.9 52.9 79.7
Dec 2017
18,612 225,225 123,442 0 71.5 27.3 53.1 80.4
Jan 2018
22,455 267,883 148,714 0 86.2 27.7 53.8 81.5
Feb 2018
16,810 210,185 115,432 0 71.5 26.5 53.2 79.7
Mar 2018
18,753 234,773 134,375 0 72.0 26.4 55.5 81.9
Apr 2018
18,148 227,073 130,569 0 72.0 26.4 55.7 82.1
May 2018
18,280 230,207 130,380 0 70.2 26.3 54.9 81.1
Jun 2018
16,723 213,509 118,686 0 66.4 25.9 53.9 79.8
Jul 2018
16,641 213,717 114,261 0 63.9 25.8 51.8 77.6
Aug 2018
11,758 153,913 69,626 0 45.2 25.3 43.8 69.1
Sep 2018
5,650 75,303 36,896 0 22.4 24.8 47.5 72.3
Oct 2018
12,001 160,312 87,223 0 46.1 24.8 52.7 77.5
Nov 2018
8,818 114,676 61,762 0 35.0 25.4 52.2 77.6
Dec 2018
16,108 207,767 116,138 0 61.9 25.6 54.2 79.8
Jan 2019
16,716 215,135 117,386 0 64.2 25.7 52.9 78.6
Feb 2019
15,456 197,949 104,456 0 65.7 25.8 51.1 77.0
Mar 2019
17,207 219,949 117,917 0 66.1 25.9 51.9 77.8
Apr 2019
16,373 210,482 113,773 0 65.0 25.7 52.4 78.1
May 2019
17,498 223,565 121,221 0 67.2 25.9 52.5 78.4
Jun 2019
16,595 213,411 115,455 0 65.9 25.7 52.4 78.1
Jul 2019
15,194 201,815 103,680 0 58.3 24.9 49.8 74.7
Aug 2019
15,680 206,767 103,848 0 60.2 25.1 48.7 73.7
Sep 2019
15,002 187,471 87,303 0 59.5 26.5 45.1 71.6
Oct 2019
15,503 193,869 95,398 0 59.5 26.4 47.7 74.1
Nov 2019
16,220 207,909 106,730 0 64.4 25.8 49.7 75.5
Dec 2019
16,729 216,390 114,850 0 64.2 25.6 51.4 77.0
Jan 2020
13,339 180,871 93,206 0 51.2 24.4 49.9 74.3
Feb 2020
12,935 179,740 91,240 0 53.1 23.8 49.2 73.0
Mar 2020
12,030 167,916 85,886 0 46.2 23.7 49.6 73.3
Apr 2020
10,612 140,038 76,064 0 42.1 25.1 52.6 77.7
May 2020
11,526 146,975 82,041 0 44.3 25.9 54.1 80.0
Jun 2020
9,929 127,528 71,453 0 39.4 25.7 54.3 80.0
Jul 2020
4,000 54,389 17,468 0 15.4 24.3 31.1 55.4
Aug 2020
-32 3,015 18 0 0.0 0.0 0.6 0.6
Sep 2020
-197 754 8 0 0.0 0.0 1.0 1.0
Oct 2020
-167 1,368 14 0 0.0 0.0 1.0 1.0
Nov 2020
-118 1,814 6 0 0.0 0.0 0.3 0.3
Dec 2020
2,311 34,482 22 0 8.9 22.2 0.1 22.2
Jan 2021
3,869 55,772 31 0 14.9 22.9 0.1 23.0
Feb 2021
4,654 65,583 49 0 19.8 23.5 0.1 23.5
Mar 2021
1,831 28,635 29 0 7.0 21.1 0.1 21.2
Apr 2021
4,792 62,303 34,163 0 19.0 25.4 53.1 78.6
May 2021
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2021
5,217 67,055 37,271 0 20.7 25.7 53.9 79.6
Jul 2021
10,747 139,173 75,447 0 41.3 25.5 52.5 78.1
Aug 2021
11,076 143,607 77,957 0 42.5 25.5 52.6 78.1
Sep 2021
10,150 130,939 71,672 0 40.3 25.6 53.0 78.7
Oct 2021
10,702 137,812 74,959 0 41.1 25.7 52.7 78.4
Nov 2021
10,122 130,198 70,912 0 40.2 25.7 52.8 78.5
Dec 2021
11,533 147,235 80,058 0 44.3 25.9 52.7 78.6
Jan 2022
10,903 137,757 76,038 0 41.9 26.2 53.5 79.7
Feb 2022
9,936 125,882 69,818 0 42.2 26.1 53.7 79.8
Mar 2022
11,924 152,509 84,796 0 45.8 25.9 53.9 79.7
Apr 2022
5,560 70,511 40,009 0 44.1 26.1 55.0 81.1

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
Remeeder House - Sheffield 72.0 % 46.2 % 25.8 % 46.8 % 700 MWh
Top Peer 87.4 % 58.2 % 29.2 % 54.8 % 91 MWh
Average Peer 60.1 % 36.8 % 23.3 % 38.3 % 1,199 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 94

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Jun 2017 to Apr 2022
Peak Demand Reduction (kWP)
17
kW
Total Generation (kWhA)
699,654
kWh
Heat Recovered
4,284
MMBtu
Gas Consumed
8,977
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

83.6
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

80.0
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.