Skip to Main Content
Search distributed energy resources in New York

Remeeder House - Blake

Overview Remeeder House - Blake

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

May 2017 to Apr 2022
718
MWh
electricity generated
Capacity
Factor
9,135
Mcf
generator fuel consumed
Electric
Efficiency
4,636
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

May 2017 to Apr 2022
Electricity Generated (kWh) Total Fuel Consumed (cf) Total Heat Used (MBtu) Heat Rejected (MBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 718,476 9,135,053 4,635,632 0 46.9 26.0 49.2 75.2
May 2017
7,671 91,111 38,037 0 29.5 27.8 40.5 68.3
Jun 2017
11,300 133,565 51,859 0 44.8 28.0 37.6 65.6
Jul 2017
17,459 206,993 84,944 0 67.0 27.9 39.8 67.7
Aug 2017
20,857 246,682 93,805 0 80.1 28.0 36.8 64.8
Sep 2017
21,823 257,451 94,457 0 86.6 28.0 35.6 63.6
Oct 2017
20,421 247,610 99,424 0 78.4 27.3 38.9 66.2
Nov 2017
18,433 227,898 106,929 0 73.1 26.7 45.5 72.2
Dec 2017
17,106 207,218 100,400 0 65.7 27.3 46.9 74.3
Jan 2018
17,644 209,571 103,895 0 67.8 27.8 48.0 75.9
Feb 2018
12,299 164,713 74,312 0 52.3 24.7 43.7 68.4
Mar 2018
18,392 228,099 115,464 0 70.6 26.7 49.1 75.7
Apr 2018
17,444 220,942 106,619 0 69.2 26.1 46.8 72.9
May 2018
16,433 211,709 101,865 0 63.1 25.7 46.6 72.3
Jun 2018
15,804 205,305 106,796 0 62.7 25.5 50.4 75.9
Jul 2018
16,277 211,971 107,079 0 62.5 25.4 48.9 74.3
Aug 2018
15,489 204,407 92,332 0 59.5 25.1 43.8 68.8
Sep 2018
13,331 173,963 77,260 0 52.9 25.3 43.0 68.4
Oct 2018
3,954 52,783 26,461 0 15.2 24.8 48.6 73.4
Nov 2018
0 0 0 0 0.0 0.0 0.0 0.0
Dec 2018
9,906 126,701 66,139 0 38.0 25.9 50.6 76.4
Jan 2019
12,957 165,253 91,142 0 49.8 25.9 53.4 79.4
Feb 2019
16,148 205,270 113,570 0 68.7 26.0 53.6 79.6
Mar 2019
17,862 227,424 126,430 0 68.6 26.0 53.9 79.8
Apr 2019
17,318 220,440 124,931 0 68.7 26.0 54.9 80.9
May 2019
17,167 220,975 124,011 0 65.9 25.7 54.4 80.1
Jun 2019
13,563 184,263 98,079 0 53.8 24.3 51.6 75.9
Jul 2019
12,939 179,803 92,729 0 49.7 23.8 50.0 73.8
Aug 2019
8,734 121,618 62,194 0 33.5 23.7 49.6 73.3
Sep 2019
696 8,843 4,595 0 2.8 26.0 50.4 76.4
Oct 2019
13,956 182,047 96,487 0 53.6 25.4 51.4 76.7
Nov 2019
15,490 201,446 105,790 0 61.5 25.4 50.9 76.3
Dec 2019
17,706 226,257 121,786 0 68.0 25.9 52.2 78.0
Jan 2020
16,971 219,866 118,950 0 65.2 25.5 52.4 78.0
Feb 2020
15,655 203,645 109,585 0 64.3 25.4 52.1 77.6
Mar 2020
15,970 207,133 111,513 0 61.3 25.5 52.2 77.7
Apr 2020
12,428 157,704 87,815 0 49.3 26.1 54.0 80.0
May 2020
13,176 165,564 90,933 0 50.6 26.3 53.2 79.5
Jun 2020
12,376 156,936 86,965 0 49.1 26.1 53.7 79.8
Jul 2020
10,411 137,916 71,722 0 40.0 25.0 50.4 75.4
Aug 2020
905 14,139 6,096 0 3.5 21.2 41.8 62.9
Sep 2020
354 7,062 2,425 0 1.4 16.6 33.3 49.8
Oct 2020
0 0 0 0 0.0 0.0 0.0 0.0
Nov 2020
0 0 0 0 0.0 0.0 0.0 0.0
Dec 2020
2,788 38,525 19,655 0 10.7 23.9 49.4 73.4
Jan 2021
4,485 59,823 31,567 0 17.2 24.8 51.1 75.9
Feb 2021
11,633 145,603 82,065 0 49.5 26.4 54.6 81.0
Mar 2021
12,370 155,316 87,252 0 47.5 26.3 54.4 80.8
Apr 2021
4,490 58,592 31,365 0 17.8 25.3 51.9 77.2
May 2021
12,324 154,952 84,264 0 47.3 26.3 52.7 79.0
Jun 2021
11,623 147,083 80,319 0 46.1 26.1 52.9 79.0
Jul 2021
11,790 151,639 79,954 0 45.3 25.7 51.1 76.8
Aug 2021
10,310 138,237 68,447 0 39.6 24.7 48.0 72.6
Sep 2021
3,103 41,058 20,317 0 12.3 25.0 48.0 72.9
Oct 2021
9,351 122,636 61,312 0 35.9 25.2 48.4 73.7
Nov 2021
11,475 147,073 80,545 0 45.5 25.8 53.1 78.9
Dec 2021
11,846 150,573 84,118 0 45.5 26.0 54.1 80.2
Jan 2022
12,666 159,555 90,110 0 48.6 26.3 54.7 81.0
Feb 2022
11,321 142,823 81,051 0 48.1 26.2 55.0 81.2
Mar 2022
12,104 152,917 86,574 0 46.5 26.2 54.9 81.0
Apr 2022
9,969 126,348 70,893 0 45.6 26.1 54.4 80.5

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
Remeeder House - Blake 75.2 % 49.2 % 26.0 % 46.9 % 718 MWh
Top Peer 87.4 % 58.2 % 29.2 % 54.8 % 91 MWh
Average Peer 60.1 % 36.8 % 23.3 % 38.3 % 1,211 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 94

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

May 2017 to Apr 2022
Peak Demand Reduction (kWP)
24
kW
Total Generation (kWhA)
718,476
kWh
Heat Recovered
4,636
MMBtu
Gas Consumed
9,135
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

87.5
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

83.5
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.