Skip to Main Content
Search distributed energy resources in New York

Madison House

Overview Madison House

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Oct 2015 to Feb 2020
1,022
MWh
electricity generated
Capacity
Factor
16,037
Mcf
generator fuel consumed
Electric
Efficiency
7,096
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Oct 2015 to Feb 2020
Electricity Generated (kWh) Total Fuel Consumed (cf) Total Heat Used (MBtu) Heat Rejected (MBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 1,022,018 16,037,407 7,095,816 2,368,562 35.6 21.1 42.9 63.9
Oct 2015
11,106 180,672 89,675 19,666 36.3 20.3 48.1 68.4
Nov 2015
11,635 187,486 97,882 14,037 21.5 20.5 50.6 71.1
Dec 2015
20,844 335,731 171,520 26,126 37.4 20.5 49.5 70.0
Jan 2016
20,785 337,967 187,566 7,808 37.2 20.3 53.8 74.1
Feb 2016
18,461 307,251 185,980 750 35.4 19.9 58.7 78.5
Mar 2016
17,994 312,381 190,791 8,384 32.2 19.1 59.2 78.2
Apr 2016
13,481 238,300 139,873 10,204 25.0 18.7 56.9 75.6
May 2016
17,832 308,420 158,480 32,714 32.0 19.1 49.8 68.9
Jun 2016
18,079 300,290 90,425 87,888 33.5 19.9 29.2 49.1
Jul 2016
16,979 299,410 79,008 92,119 30.4 18.8 25.6 44.3
Aug 2016
27,388 394,540 88,126 130,628 49.1 23.0 21.6 44.6
Sep 2016
24,667 344,840 73,016 116,812 45.7 23.7 20.5 44.2
Oct 2016
17,701 311,510 115,625 61,145 31.7 18.8 36.0 54.8
Nov 2016
20,817 331,180 185,260 28,057 38.6 20.8 54.2 75.0
Dec 2016
16,555 270,740 149,087 7,174 29.7 20.2 53.4 73.6
Jan 2017
22,704 357,040 204,012 12,558 40.7 21.0 55.4 76.4
Feb 2017
18,888 309,710 171,203 15,368 37.5 20.2 53.6 73.7
Mar 2017
24,458 371,620 211,700 16,070 43.8 21.8 55.2 77.0
Apr 2017
21,486 332,440 138,850 66,920 39.8 21.4 40.5 61.8
May 2017
23,326 348,650 122,396 88,970 41.8 22.1 34.0 56.1
Jun 2017
13,261 202,480 38,664 65,238 24.6 21.7 18.5 40.2
Jul 2017
17,043 226,810 39,896 87,610 30.5 24.9 17.0 41.9
Aug 2017
30,764 412,620 76,425 156,914 55.1 24.7 17.9 42.6
Sep 2017
27,886 392,090 88,388 132,171 51.6 23.5 21.8 45.4
Oct 2017
25,588 389,060 115,648 108,095 45.9 21.8 28.8 50.6
Nov 2017
23,428 385,400 217,688 23,463 43.4 20.1 54.7 74.8
Dec 2017
28,710 442,650 256,556 7,473 51.5 21.5 56.2 77.6
Jan 2018
22,267 348,530 200,249 8,155 39.9 21.1 55.7 76.8
Feb 2018
23,225 377,390 212,318 15,671 46.1 20.4 54.5 74.9
Mar 2018
19,849 335,890 193,326 8,810 35.6 19.5 55.8 75.3
Apr 2018
21,009 388,970 190,931 40,152 38.9 17.9 47.6 65.4
May 2018
22,688 395,260 94,683 127,166 40.7 19.0 23.2 42.2
Jun 2018
28,412 489,890 89,361 179,360 52.6 19.2 17.7 36.9
Jul 2018
24,700 450,680 78,233 163,723 44.3 18.1 16.8 34.9
Aug 2018
18,592 356,400 65,235 126,172 33.3 17.3 17.7 35.0
Sep 2018
24,264 352,350 83,869 122,429 44.9 22.8 23.1 45.8
Oct 2018
21,405 312,060 124,911 66,472 38.4 22.7 38.8 61.5
Nov 2018
25,837 366,930 206,361 22,304 47.8 23.3 54.5 77.8
Dec 2018
23,397 322,540 194,620 3,392 41.9 24.0 58.5 82.5
Jan 2019
30,572 412,030 247,126 2,416 54.8 24.5 58.1 82.7
Feb 2019
25,009 346,930 211,089 1,018 49.6 23.8 59.0 82.8
Mar 2019
8,334 120,040 71,636 281 14.9 23.0 57.8 80.8
Apr 2019
1,100 19,150 11,490 302 2.0 19.0 58.1 77.1
May 2019
2,645 51,610 24,131 4,106 4.7 16.9 45.3 62.3
Jun 2019
4,650 91,390 32,640 9,810 8.6 16.8 34.6 51.4
Jul 2019
3,570 73,390 24,367 8,480 6.4 16.1 32.2 48.3
Aug 2019
5,555 110,730 34,020 13,369 10.0 16.6 29.8 46.4
Sep 2019
1,658 31,880 16,415 2,113 3.1 17.2 49.9 67.1
Oct 2019
17,958 276,250 166,190 8,506 32.2 21.5 58.3 79.8
Nov 2019
24,981 367,610 226,298 2,248 46.3 22.5 59.7 82.1
Dec 2019
26,746 378,980 232,077 1,201 47.9 23.3 59.3 82.7
Jan 2020
24,974 366,170 226,627 1,588 44.8 22.6 60.0 82.5
Feb 2020
16,757 263,070 153,873 4,959 35.8 21.1 56.7 77.7

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
Madison House 63.9 % 42.9 % 21.1 % 35.6 % 1,022 MWh
Top Peer 88.3 % 63.1 % 25.2 % 41.4 % 220 MWh
Average Peer 61.0 % 37.7 % 23.3 % 42.7 % 939 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 84

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Oct 2015 to Feb 2020
Peak Demand Reduction (kWP)
29
kW
Total Generation (kWhA)
1,022,018
kWh
Heat Recovered
7,096
MMBtu
Gas Consumed
16,037
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

74.7
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

71.1
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.