Skip to Main Content
Search distributed energy resources in New York

Hilton - New York

This page shows facility, project, and distributed energy resource details. Click on the solid bars to show or hide details.

View Facility in Google Maps
1335 Sixth Ave
New York, NY 10019
CHP
1,750 kW
9.3 MMBtu/h
FC
200 kW
0 Btu/h

Facility Details

View Data
CategoryLodging: Hotel
Electric UtilityConsolidated Edison
Gas UtilityConsolidated Edison
NYISO ZoneJ - New York City
  • Combined Heat and Power (CHP) Project

    Elec. Gen. Capacity
    1,750 kW
    Heat Gen. Capacity
    9,320 MBtu/h
    View Plots and Tables View Data
    ProgramCHP
    Developer/InstallerAnaergiaExternal link (opens in new window)
    Data MonitoringApr 2013 – Feb 2019
    NYSERDA Contract NameHilton - New York - Anaergia
    Heat Recovery Loads MetDomestic Hot Water (DHW), Other Heat Loads
    System Redundancy (N+1)
    Grid Export Capable
    • Unit Manufacturer SDP Energy
      Unit Model MAN 250
      Elec. Gen. Rating per Unit 250 kW
      Thermal Gen. Rating per Unit 1331.4 MBtu/h
      No. of Units 7
      No. of Prime Movers7
      Primary FuelNatural Gas
      Prime MoverReciprocating Engine
      LocationOutdoor - Rooftop
      GeneratorInduction Generator
      Rated Electric Efficiency (% HHV)34.8
      Rated CHP Efficiency (% HHV)85.8
  • Fuel Cell (FC) Project

    Elec. Gen. Capacity
    200 kW
    View Plots and Tables View Data
    ProgramFuel Cell
    Developer/InstallerDoosan Fuel Cell AmericaExternal link (opens in new window)
    Data MonitoringSep 2007 – Sep 2012
    NYSERDA Contract NameHilton-New York
    Grid Export Capable
    • Unit Manufacturer UTC Power
      Unit Model Purecell 200
      Elec. Gen. Rating 200 kW
      No. of Units 1
      No. of Prime Movers1
      Primary FuelNatural Gas
      Prime MoverFuel Cell
      GeneratorInverter
      Rated Electric Efficiency (% HHV)40.0